ZHCSFI2B July 2016 – February 2017 TPS53667
PRODUCTION DATA.
The TPS53667 device is a DCAP+ mode adaptive on-time controller.
The output voltage is set using a DAC that outputs a reference in accordance with the 8-bit VID code defined in Table 1. In adaptive on-time converters, the controller varies the on-time as a function of input and output voltage to maintain a nearly constant frequency during steady-state conditions. In conventional voltage-mode constant on-time converters, each cycle begins when the output voltage crosses to a fixed reference level. However, in the TPS53667 device, the cycle begins when the current feedback reaches an error voltage level which corresponds to the amplified voltage difference between the DAC voltage and the feedback output voltage with droop. In the case of multi-phase operations, the current feedback from all the phases is summed, and is amplified using the ISUM pin to adjust the load-line. Also zero-load line operation can be easily configured with external resistor or internal NVM selection.
V3R3 is an LDO output generated from V5. It is used as internal digital circuit supply and 1-uF to 4.7-uF ceramic decoupling capacitor to GND pin is recommended.
When V5 exceeds VV5UVLOH (4.25 V typically), V3R3 begins to ramp up. The startup time for V3R3 is approximately 600 µs as shown in Figure 7.
After V3R3 has reached its operational level, the TPS53667 begins to initialize the internal circuit and reads the pinstrap configurations. This pinstrap reading completes in approximately 1.2 ms, and can communicate to the PMBus 1.5 ms after V3R3 powers up.
NOTE
This device does not require a high ENABLE signal in order for the V3R3 LDO to start up.
Use V3R3 as pull-up voltage for CSPx (to disable phases), ENABLE, VR_RDY, VR_HOT, and VR_FAULT. Because the V3R3 maximum current capability is approximately 5 mA, choose pull-up resistances carefully.
Directly tie CSP6,CSP5, CSP4, CSP3 or CSP2 to the V3R3 pin according to to disable the corresponding phase.
As shown in the Functional Block Diagram, in 6-phase continuous conduction mode, the device operates as described in Figure 8.
Starting with the condition that the high-side FETs are off and the low-side FETs are on, the summed current feedback (VISUM) is higher than the summed error amplifier output (VCOMP) and the internal ramp signal (VRAMP). ISUM falls until it hits VCOMP+VRAMP, which contains a component of the output ripple voltage. The PWM comparator senses where the two waveforms cross and triggers the on-time generator. This generates the internal SW_CLK. Each SW_CLK corresponds to one switching ON pulse for one phase.
In case of single-phase operation, every SW_CLK generates a switching pulse on the same phase. Also, VISUM corresponds to just a single-phase inductor current.
In case of multi-phase operation, the SW_CLK gets distributed to each of the phases in a cycle. This approach of using the summed inductor current and cyclically distributing the ON pulses to each phase automatically gives the required interleaving of 360 / n, where n is the number of phases.
The TPS53667 device provides independent channels of current feedback for every phase to increase the system accuracy and reduce the dependence of circuit performance on layout compared to an externally summed architecture. The current sensing signals are from TI smart power stages (at 5mV/A) (ex: CSD9549x) and are already temperature-compensated. The pins CSP1, CSP2, CSP3, CSP4, CSP5, and CSP6 are used for the individual phases of the phase current sensing.
The sensed currents are then summed together and generate a current output to IMON pin. A resistor is connected to IMON pin to generate the VIMON voltage.
where
Then the VIMON voltage translates to a digital IMON reading as shown in Equation 2.
where
When VIMON is 0.85 V, the IMON reading should be equal to IMAX.
The digital IMON then can be reported to the system by using PMBus command READ_IOUT.
A resistor between the ISUM pin and the VREF pin sets the load line in non-zero load line mode.
where
A desired zero load-line can be implemented by putting a 0 Ω between ISUM and VREF pins or by shorting the ISUM and VREF pins directly.
When there is a sudden load increase, the output voltage immediately drops. The TPS53667 device reacts to this drop in a rising voltage on the COMP pin. This rise forces the PWM pulses to come in sooner and more frequently which causes the inductor current to rapidly increase. As the inductor current reaches the new load current, the device reaches a steady-state operating condition and the PWM switching resumes the steady-state frequency.
When there is a sudden load release, the output voltage flies high. The TPS53667 device reacts to this rise in a falling voltage on the COMP pin. This drop forces the PWM pulses to be delayed until the inductor current reaches the new load current. At that point, the switching resumes and steady-state switching continues.
Please note in Figure 10 and Figure 11, the ripples on VOUT, VRAMP, and VCOMP voltages are not shown for simplicity.
The problem of overshoot in low duty-cycle synchronous buck converters is well known, and results from the output inductor having a small voltage (VOUT) with which to respond to a transient load release.
For simplicity, Figure 12 shows a single phase converter. In an ideal converter, with typical input voltage of 12 V and a 1.0-V output, the inductor has 11.0 V (12 V – 1.0 V) to respond to a transient load increase, but only 1.0 V to respond once the load releases.
With the Overshoot Reduction (OSR) feature enabled, when the summed voltage of VOUT and VDROOP exceeds the DAC voltage VDAC by the OSR value specified in the Electrical Characteristics table, the PWM pulses immediately become tri-state to turn off both the high-side and low-side FETs. When the low-side FETs are turned OFF, the energy in the inductor is partially dissipated by the body diodes. Please note the ON pulse width can be also truncated immediately regardless of the load transient timing, and this feature can further reduce the overshoot when compared to the conventional constant on-time controllers as shown in Figure 13 .
When the transient load increase becomes quite large, it becomes difficult to meet the energy demanded by the load especially at lower input voltages. Then it is necessary to quickly increase the energy in the inductors during the transient load increase. This is achieved in TPS53667 by enabling pulse overlapping. In order to maintain the interleaving of the multi-phase configuration and yet be able to have pulse-overlapping during load-insertion, the Undershoot Reduction (USR) mode is entered only when necessary. This mode is entered when the difference between DAC voltage and the summed voltage of VOUT and VDROOP exceeds the USR voltage level specified in the Electrical Characteristics table.
The waveforms in Figure 14 indicate the performance with USR. It can be seen that it is possible to eliminate undershoot by enabling USR. This allows reduced output capacitance to be used and still meets the specification.
When the transient condition is over, the interleaving of the phases is resumed.
The basic mechanism for current sharing is to sense the average phase current, then adjust the pulse width of each phase to equalize the current in each phase as shown in Figure 15. The PWM comparator (not shown) starts a pulse when the feedback voltage meets the reference. The VIN voltage charges Ct(on) through Rt(on). The pulse terminates when the voltage at Ct(on) matches the on-time reference, which normally equals the DAC voltage (VDAC).
The circuit operates in the following fashion. First assume that the 5-µs averaged value from each phase current are equal. In this case, the PWM modulator terminates at VDAC, and the normal pulse width is delivered to the system. If instead, I1 > IAVG, then an offset is subtracted from VDAC, and the pulse width for Phase 1 is shortened to reduce the phase current in Phase 1 for balancing. If I1 < IAVG, then a longer pulse is generated to increase the phase current in Phase 1 to achieve current balancing.
In TPS53667, phase overlap is allowed during both steady state and transient operation. The duty cycle is not limited to 1/n (where n is the phase number) unlike TPS53647
The DAC voltage VDAC can be changed according to Table 1.
The slew rate for a change is set by the resistor at SLEW-MODE pin, as defined in the Electrical Characteristics table.
VID Hex VALUE |
VR12.0 VOLTAGE (V) |
VR12.5 VOLTAGE (V) |
---|---|---|
00 | 0 | 0 |
01 | 0.25 | 0.50 |
02 | 0.255 | 0.51 |
03 | 0.26 | 0.52 |
04 | 0.265 | 0.53 |
05 | 0.27 | 0.54 |
06 | 0.275 | 0.55 |
07 | 0.28 | 0.56 |
08 | 0.285 | 0.57 |
09 | 0.29 | 0.58 |
0A | 0.295 | 0.59 |
0B | 0.30 | 0.60 |
0C | 0.305 | 0.61 |
0D | 0.31 | 0.62 |
0E | 0.315 | 0.63 |
0F | 0.32 | 0.64 |
10 | 0.325 | 0.65 |
11 | 0.33 | 0.66 |
12 | 0.335 | 0.67 |
13 | 0.34 | 0.68 |
14 | 0.345 | 0.69 |
15 | 0.35 | 0.70 |
16 | 0.355 | 0.71 |
17 | 0.36 | 0.72 |
18 | 0.365 | 0.73 |
19 | 0.37 | 0.74 |
1A | 0.375 | 0.75 |
1B | 0.38 | 0.76 |
1C | 0.385 | 0.77 |
1D | 0.39 | 0.78 |
1E | 0.395 | 0.79 |
1F | 0.40 | 0.80 |
20 | 0.405 | 0.81 |
21 | 0.41 | 0.82 |
22 | 0.415 | 0.83 |
23 | 0.42 | 0.84 |
24 | 0.425 | 0.85 |
25 | 0.43 | 0.86 |
26 | 0.435 | 0.87 |
27 | 0.44 | 0.88 |
28 | 0.445 | 0.89 |
29 | 0.45 | 0.90 |
2A | 0.455 | 0.91 |
2B | 0.46 | 0.92 |
2C | 0.465 | 0.93 |
2D | 0.47 | 0.94 |
2E | 0.475 | 0.95 |
2F | 0.48 | 0.96 |
30 | 0.485 | 0.97 |
31 | 0.49 | 0.98 |
32 | 0.495 | 0.99 |
33 | 0.50 | 1.00 |
34 | 0.505 | 1.01 |
35 | 0.51 | 1.02 |
36 | 0.515 | 1.03 |
37 | 0.52 | 1.04 |
38 | 0.525 | 1.05 |
39 | 0.53 | 1.06 |
3A | 0.535 | 1.07 |
3B | 0.54 | 1.08 |
3C | 0.545 | 1.09 |
3D | 0.55 | 1.10 |
3E | 0.555 | 1.11 |
3F | 0.56 | 1.12 |
40 | 0.565 | 1.13 |
41 | 0.57 | 1.14 |
42 | 0.575 | 1.15 |
43 | 0.58 | 1.16 |
44 | 0.585 | 1.17 |
45 | 0.59 | 1.18 |
46 | 0.595 | 1.19 |
47 | 0.60 | 1.20 |
48 | 0.605 | 1.21 |
49 | 0.61 | 1.22 |
4A | 0.615 | 1.23 |
4B | 0.62 | 1.24 |
4C | 0.625 | 1.25 |
4D | 0.63 | 1.26 |
4E | 0.635 | 1.27 |
4F | 0.64 | 1.28 |
50 | 0.645 | 1.29 |
51 | 0.65 | 1.30 |
52 | 0.655 | 1.31 |
53 | 0.66 | 1.32 |
54 | 0.665 | 1.33 |
55 | 0.67 | 1.34 |
56 | 0.675 | 1.35 |
57 | 0.68 | 1.36 |
58 | 0.685 | 1.37 |
59 | 0.69 | 1.38 |
5A | 0.695 | 1.39 |
5B | 0.70 | 1.40 |
5C | 0.705 | 1.41 |
5D | 0.71 | 1.42 |
5E | 0.715 | 1.43 |
5F | 0.72 | 1.44 |
60 | 0.725 | 1.45 |
61 | 0.73 | 1.46 |
62 | 0.735 | 1.47 |
63 | 0.74 | 1.48 |
64 | 0.745 | 1.49 |
65 | 0.75 | 1.50 |
66 | 0.755 | 1.51 |
67 | 0.76 | 1.52 |
68 | 0.765 | 1.53 |
69 | 0.77 | 1.54 |
6A | 0.775 | 1.55 |
6B | 0.78 | 1.56 |
6C | 0.785 | 1.57 |
6D | 0.79 | 1.58 |
6E | 0.795 | 1.59 |
6F | 0.80 | 1.60 |
70 | 0.805 | 1.61 |
71 | 0.81 | 1.62 |
72 | 0.815 | 1.63 |
73 | 0.82 | 1.64 |
74 | 0.825 | 1.65 |
75 | 0.83 | 1.66 |
76 | 0.835 | 1.67 |
77 | 0.84 | 1.68 |
78 | 0.845 | 1.69 |
79 | 0.85 | 1.70 |
7A | 0.855 | 1.71 |
7B | 0.86 | 1.72 |
7C | 0.865 | 1.73 |
7D | 0.87 | 1.74 |
7E | 0.875 | 1.75 |
7F | 0.88 | 1.76 |
80 | 0.885 | 1.77 |
81 | 0.89 | 1.78 |
82 | 0.895 | 1.79 |
83 | 0.90 | 1.80 |
84 | 0.905 | 1.81 |
85 | 0.91 | 1.82 |
86 | 0.915 | 1.83 |
87 | 0.92 | 1.84 |
88 | 0.925 | 1.85 |
89 | 0.93 | 1.86 |
8A | 0.935 | 1.87 |
8B | 0.94 | 1.88 |
8C | 0.945 | 1.89 |
8D | 0.95 | 1.90 |
8E | 0.955 | 1.91 |
8F | 0.96 | 1.92 |
90 | 0.965 | 1.93 |
91 | 0.97 | 1.94 |
92 | 0.975 | 1.95 |
93 | 0.98 | 1.96 |
94 | 0.985 | 1.97 |
95 | 0.99 | 1.98 |
96 | 0.995 | 1.99 |
97 | 1.00 | 2.00 |
98 | 1.005 | 2.01 |
99 | 1.01 | 2.02 |
9A | 1.015 | 2.03 |
9B | 1.02 | 2.04 |
9C | 1.025 | 2.05 |
9D | 1.03 | 2.06 |
9E | 1.035 | 2.07 |
9F | 1.04 | 2.08 |
A0 | 1.045 | 2.09 |
A1 | 1.05 | 2.10 |
A2 | 1.055 | 2.11 |
A3 | 1.06 | 2.12 |
A4 | 1.065 | 2.13 |
A5 | 1.07 | 2.14 |
A6 | 1.075 | 2.15 |
A7 | 1.08 | 2.16 |
A8 | 1.085 | 2.17 |
A9 | 1.09 | 2.18 |
AA | 1.095 | 2.19 |
AB | 1.10 | 2.20 |
AC | 1.105 | 2.21 |
AD | 1.11 | 2.22 |
AE | 1.115 | 2.23 |
AF | 1.12 | 2.24 |
B0 | 1.125 | 2.25 |
B1 | 1.13 | 2.26 |
B2 | 1.135 | 2.27 |
B3 | 1.14 | 2.28 |
B4 | 1.145 | 2.29 |
B5 | 1.15 | 2.30 |
B6 | 1.155 | 2.31 |
B7 | 1.16 | 2.32 |
B8 | 1.165 | 2.33 |
B9 | 1.17 | 2.34 |
BA | 1.175 | 2.35 |
BB | 1.18 | 2.36 |
BC | 1.185 | 2.37 |
BD | 1.19 | 2.38 |
BE | 1.195 | 2.39 |
BF | 1.20 | 2.40 |
C0 | 1.205 | 2.41 |
C1 | 1.21 | 2.42 |
C2 | 1.215 | 2.43 |
C3 | 1.22 | 2.44 |
C4 | 1.225 | 2.45 |
C5 | 1.23 | 2.46 |
C6 | 1.235 | 2.47 |
C7 | 1.24 | 2.48 |
C8 | 1.245 | 2.49 |
C9 | 1.25 | 2.50 |
CA | 1.255 | n/a |
CB | 1.26 | n/a |
CC | 1.265 | n/a |
CD | 1.27 | n/a |
CE | 1.275 | n/a |
CF | 1.28 | n/a |
D0 | 1.285 | n/a |
D1 | 1.29 | n/a |
D2 | 1.295 | n/a |
D3 | 1.30 | n/a |
D4 | 1.305 | n/a |
D5 | 1.31 | n/a |
D6 | 1.315 | n/a |
D7 | 1.32 | n/a |
D8 | 1.325 | n/a |
D9 | 1.33 | n/a |
DA | 1.335 | n/a |
DB | 1.34 | n/a |
DC | 1.345 | n/a |
DD | 1.35 | n/a |
DE | 1.355 | n/a |
DF | 1.36 | n/a |
E0 | 1.365 | n/a |
E1 | 1.37 | n/a |
E2 | 1.375 | n/a |
E3 | 1.38 | n/a |
E4 | 1.385 | n/a |
E5 | 1.39 | n/a |
E6 | 1.395 | n/a |
E7 | 1.40 | n/a |
E8 | 1.405 | n/a |
E9 | 1.41 | n/a |
EA | 1.415 | n/a |
EB | 1.42 | n/a |
EC | 1.425 | n/a |
ED | 1.43 | n/a |
EE | 1.435 | n/a |
EF | 1.44 | n/a |
F0 | 1.445 | n/a |
F1 | 1.45 | n/a |
F2 | 1.455 | n/a |
F3 | 1.46 | n/a |
F4 | 1.465 | n/a |
F5 | 1.47 | n/a |
F6 | 1.475 | n/a |
F7 | 1.48 | n/a |
F8 | 1.485 | n/a |
F9 | 1.49 | n/a |
FA | 1.495 | n/a |
FB | 1.50 | n/a |
FC | 1.505 | n/a |
FD | 1.51 | n/a |
FE | 1.515 | n/a |
FF | 1.52 | n/a |
The PWM and SKIP-NVM signals are output from the controller to drive the TI smart power stages. Both signals are 3.3-V logic based. The PWM signal is logic high to turn on the high-side MOSFET and logic low to turn on the low-side MOSFET. When both high-side and low-side MOSFETs are expected to be OFF, the PWM signal is driven to tri-state condition (1.7 V). The SKIP-NVM pin is asserted low during the soft-start period.
TI smart power stage (ex: CSD9549x) senses the die temperature and sends out the temperature information as a voltage through the TAO pin. In a multi-phase application, the TAO pin of the TI smart power stages are connected and then tied to the TSEN pin of the TPS53667 device. In this case, the device reports the temperature of the hottest power stage. The reported temperature can be calculated as shown in Equation 4.
where
NOTE
The maximum temperature that can be sensed is 127.9 °C. If the TSEN voltage (VTSEN ) is higher than the voltage associated to 127.9 °C, the device continues to report 127.9 °C.
TSEN signal is also used as an indicator for power stage fault. When an internal fault occurs in the TI smart power stage (CSD9549x), the power stage pulls the TAO pin high. In the default configuration, if the TSEN voltage is higher than 2.5 V, the TPS53667 device senses the fault and turns off both the high-side and the low-side MOSFETS. There is also an option to disable power stage fault as described in MFR_SPECIFIC_07[3].
During adaptive voltage scaling (AVS) operation, the voltage may become falsely adjusted to be out of ASIC operating range. The RESET function returns the voltage to the VBOOT voltage. When the voltage is out of ASIC operating range, the ASIC issues a RESET signal to the TPS53667 device, as shown in Figure 17. The device senses this signal and after a delay of greater than 1 µs, it sets an internal RESET_FAULT signal and sets VOUT_COMMAND to VBOOT. The device pulls the output voltage to the VBOOT level with the slew rate set by SLEW-MODE pin, as shown in Figure 18.
When the RESET pin signal goes high, the internal RESET_FAULT signal goes low.
The TPS53667 device continuously monitors the input voltage through the VIN pin. If the input voltage is lower than the UVLO low threshold, the device turns off. If VIN rises higher than the UVLO high threshold, the controller turns on again (if both V5 and ENABLE are high). The hysteresis is approximately 1.05 V.
VIN UVLO SETTING | TURN-ON VOLTAGE (V) | TURN-OFF VOLTAGE (V) |
---|---|---|
MFR_SPEC_16[1:0] = 00 | 4.5 | 3.5 |
MFR_SPEC_16[1:0] = 01 (Default) | 7.25 | 6.25 |
MFR_SPEC_16[1:0] = 10 | 7.9 | 6.9 |
MFR_SPEC_16[1:0] = 11 | 10.3 | 9.3 |
The TPS53667 device also monitors V5 pin voltage. If the voltage is lower than VV5UVLOL (4.05 V typical), the controller turns off. If V5 voltage comes back to be higher than VV5UVLOH (4.25 V typical), the controller turns back on (if both VIN and ENABLE are high).
The output undervoltage protection in the TPS53667 device is called tracking UVP. When the output voltage drops below (VDAC–VDROOP–VRDYL), the controller drives the PWM into a tri-state condition so that both high-side and low-side MOSFETs turn off. After a hiccup delay (22-ms typical), the device attempts to restart to VBOOT voltage. If the UVP condition continues, the UVP occurs again and the process repeats.
The OVP condition is detected when the output voltage VOUT > VDAC + tracking OVP offset (VOVPT5 for VR12.5 or VOVPT0 for VR12.0) , which is called tracking OVP. In this case the controller drives the VR_RDY pin to inactive (low state) and drives all PWM signals to logic low which turns on the low-side MOSFET to discharge the output. However the OVP threshold is blanked during a VDAC change. In order to continually protect the load, there is second OVP level (fixed OVP). The second OVP level is fixed at VOVPH5 (VR12.5) or VOVPH0 (VR12.0) is active during VDAC change. If the fixed OVP condition is detected, the device drives the VR_RDY pin to inactive (logic low) and drives the PWM signals to logic low in order to turn on the low-side MOSFET. The controller remains in this state until the ENABLE or V5 is re-cycled.
For both tracking OVP and fixed OVP, the controller will try to restart after a hiccup delay (~22ms). If the OV condition still exists, the controller will pull PWM signal to logic low and enter into anther hiccup cycle. If after 3 hiccup cycles, the OV condition still exists, the controller will latch PWM signal to logic low until ENABLE or V5 is re-cycled.
When ENABLE is low, and output voltage is higher than VOVPFP (2.75 V typical), the OVP condition is detected, which is called Pre-bias OVP. The device then drives the PWM signals to logic low. The device latches the pre-bias OVP. The latch can be cleared only by recycling V5.
The TPS53667 device includes a valley-current-based limit function by using a per-phase OCL comparator. A resistor connected between the OCL-R pin and the VREF pin generates the OCL comparison threshold.
Using the valley current limit, the OCL current level can be selected using Equation 5. To set the per-phase OCL threshold, subtract half of the ripple current from the maximum average current and select the OCL threshold specified in the table equal or slight lower than IOCL.
where
This instantaneous current sense voltage VCSPx is compared to the OCL threshold. If the current sense voltage at OCL comparator goes above the OCL threshold, the device delays the next ON pulse until the current sense voltage drops below the OCL threshold. In this case, the output voltage continues to drop until the UVP threshold is reached.
Another overcurrent protection (OCP) is based on the current sensed through IMON pin of the device. When the digitized IMON is higher than OC_FAULT_LIMIT (1.25× IMAX by default), the controller turns off both high-side and low-side MOSFETS and enters into hiccup mode until the overcurrent condition is removed.
TPS53667 can detect faulty phases with the current sharing warning feature. If the current of a certain phase is lower than the average current by certain threshold (set by MFR_SPECiFIC_19, default is 8A), the controller can turn off the faulty phase while keeping the other phases in operation (This is also configurable by MFR_SPECIFIC_19[7]). The faulty phase can be read from STATUS_MFR_SPECIFIC[5:3].
The phase interleaving is not adjusted when the faulty phase is turned off. The controller phase interleaving operates as if the faulty phase still is still operating. This behavior has the affect of slightly increasing the output voltage ripple.
When there are only two phases in operation, this feature is disabled. For example, even if one of the phases has current lower than average, it does not turn off.
Individual phases can also be turned off by using the PMBus command MFR_SPECIFIC_24(0xE8). Please see MFR_SPECIFIC_24 (E8h)section for more details.
The MFR_SPECIFIC_24 setting can be effective before the controller is enabled. For example, when a certain phase is turned off by MFR_SPECIFIC_24 before Enable goes high, this phase does not turn on after Enable.
Phase Shedding is enabled with MFR_SPECIFIC_13[4]. Phase shedding allows the user to optimize efficiency over a wider range of loads. Using only one or two phases is often more efficient when the load is drawing a smaller amount of current, than using all six phases.
The points at which phases are shed can be set by MFR_SPECIFIC_15 (Dynamic Phase Shedding Thresholds) (DFh).
When the sensed temperature through TSEN pin is higher than the over temperature fault threshold OTPTHLD(125°C by default), the controller turns off high-side and low-side MOSFETS. The power stages cool down and TSEN voltage drops. When the sensed temperature is 15°C (OTPHYS) lower than the over temperature fault threshold, the controller restarts to the VBOOT voltage.
When the sensed temperature is higher than the maximim temperature specification TMAX, (110°C by default), the device pulls the VR_HOT pin low. This adjustment provides a warning signal to the load.
NOTE
Only the PMBus interface can establish the maximum temperature (TMAX) setting. NVM does not store this setting.
VR_FAULT is used as an indication of severe fault. VR_FAULT wil be pulled low when the below fault occurs:
CSP1 | CSP2 | CSP3 | CSP4 | CSP5 | CSP6 | MAXIMUM ACTIVE PHASES |
---|---|---|---|---|---|---|
IOUT1 | V3R3 | n/a | n/a | n/a | n/a | 1 |
IOUT1 | IOUT2 | V3R3 | n/a | n/a | n/a | 2 |
IOUT1 | IOUT2 | IOUT3 | V3R3 | n/a | n/a | 3 |
IOUT1 | IOUT2 | IOUT3 | IOUT4 | V3R3 | n/a | 4 |
IOUT1 | IOUT2 | IOUT3 | IOUT4 | IOUT5 | V3R3 | 5 |
IOUT1 | IOUT2 | IOUT3 | IOUT4 | IOUT5 | IOUT6 | 6 |
When SKIP-NVM pin is connected to GND with ≤ 20-kΩ resistor, the resistors connected to O-USR, F-IMAX, SLEW-MODE, OCL-R, VBOOT and ADDR-TRISE determine the associated configurations. If SKIP-NVM pin is connected to GND with ≥ 100-kΩ resistor, these configurations are determined by NVM settings. Please note the address setting is determined only by the resistors on the ADDR-TRISE pin and cannot be set by NVM. When the V3R3 pin powers up, the following information is latched for normal operations, and can be changed via the PMBus interface. The Electrical Characteristics table defines the values of the selections.
In general, the NVM provides more selection than pinstrap configurations. For example, pinstrap for switching frequency offers 3-bit, 8 selections, which correlates to MFR_SPEC_12<6:4>. Alternatively, NVM provides 4-bit, 16 selections.
The resistor from F-IMAX pin to GND sets the switching frequency from 300 kHz to 1 MHz. See the Electrical Characteristics table for the resistor settings corresponding to each frequency selection. Please note that the operating frequency is a quasi-fixed frequency in the sense that the ON time is fixed based on the input voltage (at the VIN pin) and output voltage (set by VID). The OFF time varies based on various factors such as load and power-stage components.
The max current information of the load(IMAX) can be set by the voltage on the F-IMAX pin. See the Electrical Characteristics table for the details. The default OCP fault trigger level is 125% of IMAX.
The boot voltage is the controller voltage at start-up to before any output voltage change by the VOUT_COMMAND. If there is no further output voltage adjustment, the output voltage remains at the boot voltage level.
The resistor from the VBOOT pin to GND and the voltage level on this pin set 7 high bits of the boot voltage. The lowest bit is set by the ADDR-TRISE pin. See the Electrical Characteristics table for the resistor settings corresponding to boot voltage selections.
The resistor from the OCL-R pin to GND and the voltage level on this pin set the per-phase OCL level. See the Electrical Characteristics table for the details.
The resistor from the O-USR pin to GND and the voltage on O-USR pin set the OSR and USR levels. See the Electrical Characteristics table for details.
The VOUT change slew rate is set by the resistor from the SLEW-MODE pin to GND. See the Electrical Characteristics table for details.
The TPS53667 device supports different operating modes, including VR12.0/VR12.5, phase interleaving mode, dynamic phase shedding, and zero load-line. The voltage on SLEW-MODE pin sets the desired operating modes.
The resistor from the ADDR-TRISE pin to GND and the voltage on ADDR-TRISE pin set the slew rate of soft start and the address of PMBus interface. See the Electrical Characteristics table for details.
The internal ramp can be set by the voltage on the OCL-R pin. See the Electrical Characteristics table for details.
The maximum active phase numbers can be selected by connecting CSP2, CSP3, CSP4, CSP5 or CSP6 to the V3R3. See Table 3 for details. The device latches this configuration when V3R3 powers up.
Table 4 summarizes the functions controlled with pin-strap resistors. For details of each setting please refer to the Electrical Characteristics table. For more information on VID encoding see the VID section.
FUNCTION | PIN | DESCRIPTION | |
---|---|---|---|
NAME | NO. | ||
Slew Rate | SLEW-MODE | 29 | Voltage divider to VREF pin. A pin-strap resistor (RSLEW-MODE) connected between this pin and GND sets one of eight possible slew rates. |
Mode | SLEW-MODE | 29 | The voltage level (VSLEW-MODE) sets 4-bit operation modes. -Bit 7 for DAC mode (1 for VR12.0; 0 for VR12.5). -Bit 6 for the 4-phase interleaving mode (1 for 1/3 and 2/4 two phase interleaving; 0 for 4 phase interleaving individually).-Bit 4 for enabling dynamic phase add or drop (1 for enable; 0 for disable). -Bit 3 sets zero load-line (1 for zero load-line; 0 for non-zero load-line)The device latches these settings when V3R3 powers up. |
Overshoot reduction | O-USR | 30 | Voltage divider to VREF pin. A pin-strap resistor (RO-USR) connected between this pin and GND selects 1 of 7 OSR thresholds or OFF. |
Undershoot reduction | O-USR | 30 | The voltage level (VO-USR) sets 1 of 7 USR levels or OFF. The device latches these settings when V3R3 powers up. |
Voltage boot | VBOOT | 31 | Voltage divider to VREF pin. A pin-strap resistor (RVBOOT) connected between this pin and GND sets 3 bits (B[3:1]). The voltage level (VBOOT) sets 4 bits (B[7:4]). The total 7 bit sets 7 of 8 bits of VID of VBOOT(B[7:1]).The device latches these settings when V3R3 powers up. |
ADDR-TRISE | 28 | Voltage divider to VREF pin. A pin-strap resistor (RADDR-TRISE) connected between this pin and GND sets 3-bits. -Bit 2 and Bit 1 set the rise slew rate (TRISE).-Bit 0 Selects the LSB of BOOT voltage. The voltage (VADDR-TRISE) sets 4 bits PMBus address.The device latches these settings when V3R3 powers up. |
|
Rise slew rate | ADDR-TRISE | 28 | Voltage divider to VREF pin. A pin-strap resistor (RADDR-TRISE) connected between this pin and GND sets 3-bits. -Bit 2 and Bit 1 set the rise slew rate (TRISE).-Bit 0 Selects the LSB of BOOT voltage. -The voltage (VADDR-TRISE) sets 4 bits PMBus address.The device latches these settings when V3R3 powers up |
Frequency | F-IMAX | 32 | Voltage divider to VREF pin. A pin-strap resistor (RF-IMAX) connected between this pin and GND sets the operating frequency of the controller. |
Current limit | F-IMAX | 32 | The voltage level (VF-IMAX) sets the maximum operating current of the converter. The IMAX value is an 8-bit A/D where VF-IMAX = VVREF × IMAX / 255. Both are latched at V3R3 power-up. |
Overcurrent limit | OCL-R | 1 | Voltage divider to VREF pin. A pin-strap resistor (ROCL-R) connected between this pin and GND and the voltage level (VOCL-R) selects one of 16 OCL levels (per phase current-limit). |
Ramp | OCL-R | 1 | VOCL-R sets one of four RAMP levels. The device latches these settings when the V3R3 pin powers up. |
Table 5 lists the default settings in NVM where the shaded rows denote register functions that are configured by associated pins in pinstrap mode.
REGISTER | FUNCTION | DEFAULT VALUES | |||||||
---|---|---|---|---|---|---|---|---|---|
bit 7 | bit 6 | bit 5 | bit 4 | bit 3 | bit 2 | bit 1 | bit 0 | ||
MFR_SPECIFIC_13 [2:0] | Slew Rate | — | 0 | 0 | 1 | ||||
MFR_SPECIFIC_13 [7:3] | Mode | 1 | 0 | 0 | 0 | 1 | — | ||
MFR_SPECIFIC_09 [2:0] | OSR | — | 1 | 1 | 1 | ||||
MFR_SPECIFIC_09 [6:4] | USR | — | 1 | 1 | 1 | — | |||
MFR_SPECIFIC_11 [7:0] | VBOOT | 1 | 0 | 0 | 1 | 0 | 1 | 1 | 1 |
MFR_SPECIFIC_12 [1:0] | TRISE | — | 0 | 0 | |||||
MFR_SPECIFIC_12[7:4] | Frequency | 0 | 0 | 1 | 0 | — | |||
MFR_SPECIFIC_10 [7:0] | IMAX | 1 | 0 | 1 | 1 | 0 | 1 | 0 | 0 |
MFR_SPECIFIC_00 [3:0] | OCL | — | 1 | 0 | 0 | 0 | |||
MFR_SPECIFIC_14[2:0] | RAMP | — | 1 | 1 | 0 | ||||
MFR_SPECIFIC_07 [0] | Soft-start slew rate | — | 0 | ||||||
MFR_SPECIFIC_07 [1] | OSR_TRISTATE | — | 1 | — | |||||
MFR_SPECIFIC_07 [2] | SLEW_FAST | — | 0 | — | |||||
MFR_SPECIFIC_07 [3] | Power Stage Fault Disable | — | 0 | — | |||||
MFR_SPECIFIC_07 [4] | OV Hiccup Disable | — | 0 | — | |||||
MFR_SPECIFIC_16 [1:0] | VIN UVLO | — | 0 | 1 | |||||
MFR_SPECIFIC_15 [3] | DPS_TH_LOW | — | 1 | — | |||||
MFR_SPECIFIC_15 [2:0] | DPS_TH_HIGH | — | 0 | 0 | 1 | ||||
MFR_SPECIFIC_19 [3] | Current Sharing Warning Response | — | 0 | — | |||||
MFR_SPECIFIC_19 [2:0] | Current Sharing Warning Threshold | — | 0 | 1 | 1 | ||||
MFR_SPECIFIC_21 [4:3] | Tracking OV OFFSET | — | 0 | 1 | — | ||||
MFR_SPECIFIC_21 [2:0] | Fixed OV OFFSET | — | 1 | 1 | 1 | ||||
MFR_SPECIFIC_22 [2:0] | UV OFFSET | — | 0 | 1 | 1 | ||||
MFR_SPECIFIC_05 [7:0] | VOUT OFFSET | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
MFR_ID | — | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 0 |
MFR_MODEL | 0 | 1 | 0 | 0 | 0 | 1 | 1 | 1 | |
MFR_REVISION [3:0] | — | 0 | 0 | 0 | 0 | ||||
MFR_DATE | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Figure 19 shows the diagram for a 6-Phase application with smart power stage (CSD95490Q5MC) and pinstrap configurations.
Figure 20 shows the diagram for a 6-Phase application with smart power stage (CSD95490Q5MC) and NVM configurations.
The TPS53667 device supports different types of fault protections, and the warning or fault reports can be found in the corresponding PMBus registers. The TPS53667 also supports VR_FAULT to indicate catastrophic faults to the system. If the fault causes the controller to latch-off, then V5 or EN re-cycling is required to clear the latched faults. Only V5 recycling can clear PRE_OVF .
FAULT NAME | DESCRIPTIONS | LATCH-OFF | ALERT | REPORT |
---|---|---|---|---|
VOLTAGE | ||||
PRE_OVF | VOUT > VOVPFP | Y | VR_FAULT
PMB_ALERT |
PMBus |
OVF | VOUT > VID + VOVPT5/0 or VOUT> VOVPF5 | Y | VR_FAULT
PMB_ALERT |
PMBus |
UVF | VOUT < VID – VRDYL – VDROOP | N | PMB_ALERT | PMBus |
VIN_OVF | VVIN > VIN_OV_FAULT_LIMIT when the controller is enabled | N | PMB_ALERT | PMBus |
VIN_UVF | VVIN < VINUVLO when the controller is enabled | N | PMB_ALERT | PMBus |
CURRENT | ||||
OCF | IOUT ≥ IOUT_OC_FAULT_LIMIT | N | PMB_ALERT | PMBus |
OCW | IO ≥ IOUT_OC_WARN_LIMIT | N | PMB_ALERT | PMBus |
IOCF | IIN ≥ IIN_OC_FAULT_LIMIT | Y | VR_FAULT
PMB_ALERT |
PMBus |
IOCW | IIN ≥ IIN_OC_WARN_LIMIT | N | PMB_ALERT | PMBus |
TEMPERATURE | ||||
OTF | Tsen ≥ OT_FAULT_LIMIT | N | VR_FAULT
PMB_ALERT |
PMBus |
OTW | Tsen ≥ OT_WARNING_LIMIT | N | PMB_ALERT | PMBus |
TMAX_F | Tsen≥ TMAX | N | VR_HOT | |
TS_VREFF | TSEN pin short to VREF | Y | PMB_ALERT | PMBus |
TS_GND | TSEN pin short to GND | Y | PMB_ALERT | PMBus |
TS_PS | VTSEN > 2.5 V | Y | VR_FAULT
PMB_ALERT |
PMBus |
The TPS53667 device has a dedicated pin (ADDR-TRISE) for determining the address for the PMBus communication. The device supports a total of 16 possible addresses. See the Electrical Characteristics table for details.
The TPS53667 device supports only PMBus command sets listed in Table 7. In pinstrap mode, the default state of all the configuration registers (shaded rows in Table 5) should be detected from pinstrap settings, but users can overwrite the settings via PMBus after the power-up sequence is complete. In NVM mode, the default values can be found in the register descriptions.
Timing and electrical characteristics of the PMBus can be found in the PMB Power Management Protocol Specification, Part 1, revision 1.1 available at http://PMBus.org. The TPS53667 device supports both the 100-kHz and 400-kHz bus timing requirements. The TPS53667 device does not stretch pulses on the PMBus when communicating with the master device.
Communication over the TPS53667 device PMBus interface can support the packet error checking (PEC) scheme if desired. If the master supplies CLK pulses for the PEC byte, PEC is used. If the CLK pulses are not present before a STOP, the PEC is not used.
The TPS53667 device supports a subset of the commands in the PMBus 1.1 specification. Most of the controller parameters can be programmed using the PMBus and stored as defaults for later use. All commands that require data input or output use the literal format. The exponent of the data words is fixed at a reasonable value for the command and altering the exponent is not supported. Direct format data input or output is not supported by the TPS53667 device. See the Supported PMBus Commands section for specific details.
The TPS53667 device also supports the SMBALERT response protocol. The SMBALERT response protocol is a mechanism by which a slave (the TPS53667 device) can alert the bus master that it wants to talk. The master processes this event and simultaneously accesses all slaves on the bus (that support the protocol) through the alert response address. Only the slave that caused the alert acknowledges this request. The host performs a modified receive byte operation to get the slave’s address. At this point, the master can use the PMBus status commands to query the slave that caused the alert. For more information on the SMBus alert response protocol, see the System Management Bus (SMBus) specification.
The TPS53667 device contains non-volatile memory that is used to store configuration settings and scale factors. The settings programmed into the device are not automatically saved into this non-volatile memory though. The STORE_DEFAULT_ALL command must be used to commit the current settings to non-volatile memory as device defaults. The settings that are capable of being stored in non-volatile memory are noted in their detailed descriptions.
The TPS53667 device can operate in either standard mode (100kbit/s) or fast mode (400kbit/s). Connection for the PMBus interface should follow the High Power DC specifications given in Section 3.1.3 of the System Management Bus (SMBus) Specification V2.0 for the 400-kHz bus speed or the Low Power DC specifications in Section 3.1.2. The complete SMBus specification is available from the SMBus website, smbus.org.
The TPS53667 device supports both linear and VID data formats. The linear data format is used for all telemetry reporting data, and VID formatting for certain other commands. (see the Supported PMBus Commands section for more details on which command supports each data type). Examples of commands that support VID formatting include VOUT_MODE (Read-only Byte) and VOUT_COMMAND (Read/Write Word). An example of each can be seen below in Figure 21 and Figure 22.
The Linear Data Format is a two byte value with:
The relation between Y, N, and the real world value is as shown in Equation 6.
where
Note that devices that use the Linear format must accept and be able to process any value of N.
The TPS53667 device is a PMBus-compliant device. Figure 24 through Figure 35 show the major communication protocols used. For full details on the PMBus communication protocols, please visit http://pmbus.org.
The TPS53667 device has a dedicated pin (ADDR-TRISE) for determining the address for the PMBus communication. The device supports a total of 16 possible addresses as listed in the Electrical Characteristics table.
The TPS53667 device supports only PMBus command sets listed in the Electrical Characteristics table. In pinstrap mode, the default state of all the configuration registers should be detected from pin strap settings, but users can overwrite the settings via PMBus after the power-up sequence is complete. The pin strap settings can be found in the Electrical Characteristics table.
The TPS53667 device supports the following commands from the PMBus 1.1 specification.
Format | N/A |
Description | The OPERATION command is used to turn the device output on or off in conjunction with the input from the ENABLE pin. It is also used to set the output voltage to the upper or lower MARGIN levels. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
ON_OFF | SOFT_OFF | OPMARGIN | IIN_OC_VRHOT | ||||
R/W | R-0 | R/W | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | ON_OFF | R/W | 0 | — | The On/Off bit is used to enable the IC via PMBus. The necessary condition for this bit to be effective is that the CMD bit in the ON_OFF CONFIG register is set high. However, the CMD bit being high is not a sufficient condition to enable the IC via the On bit, as specified below: 0: (Default) The device output is not enabled via PMBus. 1: The device output is enabled if: MMMa. The supply voltage VIN is greater than the VIN_UVLO threshold, the cmd bit is high, and MMMb. The bit CP in the ON_OFF CONFIG register is low, or MMMc. The bit CP is high and the ENABLE pin is asserted. |
6 | SOFT_OFF | R | 0 | — | This bit is not supported and always set to 0 on this device. 0: No Soft off 1: Not Supported. |
5-2 | OPMARGIN | R/W | 0 | — | If Margin Low is enabled, load the value from the VOUT_MARGIN_LOW register. If Margin High is enabled, load the value from the VOUT_MARGIN_HIGH register. 00xx: Turn off VOUT margin function 0101: Turn on VOUT margin low and ignore fault 0110: Turn on VOUT margin low and act on fault 1001: Turn on VOUT margin high and ignore fault 1010: Turn on VOUT margin high and act on fault |
1-0 | IIN_OC_VRHOT | R/W | 00 | — | This bit sets the option of asserting VRHOT when IIN_OC_WARN_LIMIT is detected. 01: VRHOT assertion ON with IIN_OC_WARN_LIMIT detection others: VRHOT assertion OFF with IIN_OC_WARN_LIMIT detection |
Format | N/A |
Description | The ON_OFF_CONFIG command configures the combination of CONTROL pin input and serial bus commands needed to turn the unit on and off. This includes how the unit responds when power is applied. |
Default | 17h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | PU | CMD | CP | PL | SP | ||
R-000 | R-1 | R/W | R/W | R-1 | R-1 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7-5 | Reserved | R | 000 | — | Always set to 0. |
4 | PU | R | 1 | — | This bit is not supported and always set to 1 on this device. 0: Not supported. 1: Device will act on ENABLE pin assertion and/or ON_OFF bit (OPERATION<7>). |
3 | CMD | R/W | 0 | — | The CMD bit controls how the device responds to the OPERATION<7> bit. 0: (Default) Device ignores the ON_OFF OPERATION<7> bit. 1: Device responds to the ON_OFF OPERATION<7> bit. |
2 | CP | R/W | 1 | — | The CP bit controls how the device responds to the ENABLE pin 0: Device ignores the ENABLE pin, and ON/OFF is controlled only by the OPERATION command 1: Device responds to the ENABLE pin. |
1 | PL | R | 1 | — | This bit is not supported and always set to 1 on this device. 0: Not supported. 1: ENABLE pin has active high polarity. |
0 | SP | R | 1 | — | This bit is not supported and always set to 1 on this device. 0: Not supported. 1: Turn off output as fast as possible. |
Format | N/A |
Description | Clears any faults bits that have been set. At the same time, simultaneously clears all bits in all status registers and negates the PMB_ALERT signal output if it is asserted. The CLEAR_FAULTS command does not cause a unit that has latched off for a condition to restart. If the fault remains present when the bit is cleared, the fault bit is reset and the host notified by the usual means. |
Default | NONE |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
— | — | — | — | — | — | — | — |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7-0 | N/A | — | — | — | No data bytes are sent, only the command code is sent. |
Format | N/A |
Description | The WRITE_PROTECT command is used to control writing to the PMBus device. The intent of this command is to provide protection against accidental changes. This command has one data byte as described below. NOTE: Invalid data written to WRITE_PROTECT[7:5] causes the ’CML’ bit in the STATUS_BYTE and the ‘US_DATA’ bit in the STATUS_CML registers to be set. Invalid data also results in no write protection. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
bit7 | bit6 | bit5 | Reserved | ||||
R/W | R/W | R/W | R-0 0000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | bit7 | R/W | 0 | — | 0: (Default) See Table 12. 1: Disable all writes except for the WRITE_PROTECT command (bit5 and bit6 must be 0 to be valid). |
6 | bit6 | R/W | 0 | — | 0: (Default) See Table 12. 1: Disable all writes except for the WRITE_PROTECT and OPERATION commands (bit5 and bit7 must be 0 to be valid). |
5 | bit5 | R/W | 0 | — | 0: (Default) See Table 12. 1: Disable all writes except for the WRITE_PROTECT, OPERATION, and ON_OFF_CONFIG commands (bit6 and bit7 must be 0 to be valid). |
4:0 | Reserved | R | 0 0000 | — | Always set to 0. |
Data Byte Value | Action |
---|---|
1000 0000 | Disables all writes except to the WRITE_PROTECT command. |
0100 0000 | Disables all writes except to the WRITE_PROTECT and OPERATION commands. |
0010 0000 | Disables all writes to the WRITE_PROTECT, OPERATION, ON_OFF_CONFIG and VOUT_COMMAND commands. |
0000 0000 | Enable writes to all commands |
Others | Invalid data. |
Format | N/A |
Description | The STORE_DEFAULT_ALL command instructs the PMBus device to copy the entire contents of the Operating Memory to the matching locations in the non-volatile Default Store memory. Any items in the Operating Memory that do not have matching locations in the Default Store are ignored. Following a STORE_DEFAULT_ALL command, the following registers return to the default values regardless of the values in the Operating Memory:
|
Default | NONE |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
— | — | — | — | — | — | — | — |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | N/A | — | — | — | No data bytes are sent, only the command code is sent. |
Format | N/A |
Description | The RESTORE_DEFAULT_ALL command instructs the PMBus device to copy the entire contents of the non-volatile Default Store memory to the matching locations in the Operating Memory. The values in the Operating Memory are overwritten by the value retrieved from the Default Store. Any items in Default Store that do not have matching locations in the Operating Memory are ignored. |
Default | NONE |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
— | — | — | — | — | — | — | — |
Bit | Field | Type | Reset | Description |
---|---|---|---|---|
7:0 | N/A | — | — | No data bytes are sent, only the command code is sent. |
Format | N/A |
Description | This command provides a way for a host system to determine some key capabilities of this PMBus device. |
Default | B0h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
PEC | SPD | PMBALERT | Reserved | ||||
R-1 | R-01 | R-1 | R-0000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | PEC | R | 1 | — | Packet Error Checking is supported. 1: Default |
6:5 | SPD | R | 01 | — | Maximum supported bus speed is 400 kHz. 01: Default |
4 | PMBALERT | R | 1 | — | This device does have a PMBALERT pin and does support the SMBus Alert Response Protocol. 1: Default |
3:0 | Reserved | R | 0000 | — | Always set to 0. |
Format | VID |
Description | The PMBus specification dictates that the data word for the VOUT_MODE command is one byte that consists of a 3-bit Mode and 5-bit parameter, as shown below. This command is read-only. If the host sends a VOUT_MODE command for writing, the device will reject the command and declare a communication fault for invalid data and respond as described in PMBus specification II section 10.2.2. |
Default | 21h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
DATA_MODE | DATA_PARAMETER | ||||||
R-001 | R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:5 | DATA_MODE | R | 001 | — | 001: VID mode. |
4:0 | DATA_PARAMETER | R | 0 0001 | — | 00010: For VR12.5 Mode 00001: For VR12.0 Mode |
Format | VID |
Description | VOUT_COMMAND causes the device to set its output voltage to the commanded value with two data bytes. These data bytes consist of a right-justified VID code with VID0 in bit 0 of the lower data byte, VID1 in bit 1 of the lower byte and so forth. The VID table mapping is determined by the selected VID protocols (VR12.0 or VR12.5) from SLEW_MODE pin or MFR_SPECIFIC_13. |
Default | VBOOT |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
Reserved | |||||||
R-0000 0000 | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | Reserved | R | 0000 0000 | — | Always set to 0. |
7:0 | VOUT | R/W | — | Used to set the commanded VOUT. Cannot be set to a level above the value set by VOUT_MAX. |
Format | VID |
Description | The VOUT_MAX command sets an upper limit on the output voltage that the unit can command regardless of any other commands or combinations. The intent of this command is to provide a safeguard against a user accidentally setting the output voltage to a possibly destructive level. The device detects that an attempt has been made to program the output to a voltage greater than the value set by the VOUT_MAX command. This will then be treated as a warning condition and not a fault condition. If an attempt is made to program the output voltage higher than the limit set by this command, the device responds as follows:
|
Default | 00FFh . |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
Reserved | |||||||
R-0000 0000 | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_MAX | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | Reserved | R | 0000 0000 | — | Always set to 0. |
7:0 | VOUT_MAX | R/W | 1111 1111 | — | Used to set the maximum VOUT of the device. |
Format | VID |
Description | The VOUT_MARGIN_HIGH command loads the unit with the voltage to which the output is to be changed when the OPERATION command is set to Margin High. The data bytes are two bytes, which are in right-justified VID format. The VID table mapping determined by the selected VID protocols from the SLEW_MODE pin or MFR_SPECIFIC_13. |
Default | 0000h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
Reserved | |||||||
R-0000 0000 | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_MARGIN_HIGH | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | Reserved | R | 0000 0000 | — | Always set to 0. |
7:0 | VOUT_MARGIN_HIGH | R/W | 0000 0000 | — | Used to set the value for the VOUT Margin High. |
Format | VID |
Description | The VOUT_MARGIN_LOW command loads the unit with the voltage to which the output is to be changed when the OPERATION command is set to Margin Low. The data bytes are two bytes, which are in right-justified VID format. The VID table mapping determined by the selected VID protocols from the SLEW_MODE pin or MFR_SPECIFIC_13. |
Default | 0000h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
Reserved | |||||||
R-0000 0000 | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_MARGIN_LOW | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | Reserved | R | 0000 0000 | — | Always set to 0. |
7:0 | VOUT_MARGIN_LOW | R/W | 0000 0000 | — | Used to set the value for the VOUT Margin Low. |
Format | Linear |
Description | The IOUT_CAL_OFFSET command sets the value of compensation for offset errors in the READ_IOUT command, in amperes. |
Default | 0000h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
IOCAL_OFS_EXPONENT | IOCAL_OFS_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
IOCAL_OFS_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | IOCAL_OFS_EXPONENT | R/W | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | IOCAL_OFS_MANTISSA | R/W | — | 11-bit, two's complement mantissa. |
Format | N/A |
Description | The VOUT_OV_FAULT_RESPONSE command instructs the device on what action to take in response to an output overvoltage fault. Upon triggering the overvoltage fault, the controller is latched off, and the following actions are taken:
|
Default | 9Ah |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_OV_FAULT_RESPONSE | |||||||
R-1000 0000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | VOUT_OV_FAULT_RESPONSE | R | 1000 0000 | — | Upon triggering the overvoltage fault, the controller will shut the device down immediately and will not attempt to restart. The output remains disabled until the fault is cleared. |
Format | N/A |
Description | The VOUT_UV_FAULT_RESPONSE instructs the device on what action to take in response to an output undervoltage fault. Upon triggering the undervotlage fault, the following actions are taken:
|
Default | BAh |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_UV_FAULT_RESPONSE | |||||||
R-1011 1010 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | VOUT_UV_FAULT_RESPONSE | R | 1011 1010 | — | Upon triggering the undervoltage fault, the controller will shut the device down immediately and will attempt to restart after a 22 ms delay. |
Format | Linear |
Description | The IOUT_OC_FAULT_LIMIT command sets the value of the output current, in amperes, that causes an overcurrent fault condition. Upon triggering the overcurrent fault, the following actions are taken:
|
Default | 125% IMAX |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
OCF_LIMIT_EXPONENT | OCF_LIMIT_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
OCF_LIMIT_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | OCF_LIMIT_EXPONENT | R/W | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | OCF_LIMIT_MANTISSA | R/W | — | 11-bit, two's complement mantissa. |
Format | N/A |
Description | The IOUT_OC_FAULT_RESPONSE instructs the device on what action to take in response to an output overcurrent fault. Upon triggering the overcurrent fault, the controller is latched off, and the following actions are taken:
|
Default | FAh |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
IOUT_OC_FAULT_RESPONSE | |||||||
R-1111 1010 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | IOUT_OC_FAULT_RESPONSE | R | 1111 1010 | — | Upon triggering the overcurrent fault, the controller immediately shuts down the device and attempts to restart after a 22 ms delay. |
Format | Linear |
Description | The IOUT_OC_WARN_LIMIT command sets the value of the output current, in amperes, that causes an output overcurrent warning condition. Upon triggering the overcurrent warning, the following actions are taken:
|
Default | IMAX |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
OCW_LIMIT_EXPONENT | OCW_LIMIT_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
OCW_LIMIT_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | OCW_LIMIT_EXPONENT | R/W | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | OCW_LIMIT_MANTISSA | R/W | — | 11-bit, two's complement mantissa. |
Format | Linear |
Description | The OT_FAULT_LIMIT command sets the value of the temperature limit, in degrees Celsius, that causes an over-temperature fault condition. The default value is 125C°. Upon triggering the over-temperature fault, the following actions are taken:
|
Default | 007Dh |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
OT_LIMIT_EXPONENT | OT_LIMIT_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
OT_LIMIT_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | OT_LIMIT_EXPONENT | R/W | 0000 0 | — | 5-bit, two's complement exponent (scaling factor). |
10:0 | OT_LIMIT_MANTISSA | R/W | 000 0111 1101 | — | 11-bit, two's complement mantissa. |
Format | N/A |
Description | The OT_FAULT_RESPONSE instructs the device on what action to take in response to an over-temperature fault. Upon triggering the over-temperature fault, the controller shuts off and attempts to restart when the temperature reduces by 15C°, and the following actions are taken:
|
Default | F8h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
OT_FAULT_RESPONSE | |||||||
R-1111 1000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | OT_FAULT_RESPONSE | R | 1111 1000 | — | Upon triggering the over-temperature fault, the device will shut down immediately (disables the output), and will restart when the temperature goes 15 degree Celsius below OT _FAULT_LIMIT. |
Format | Linear |
Description | The OT_WARN_LIMIT command sets the temperature, in degrees Celsius, at which it should indicate an over-temperature warning condition. The default value is 95C. Upon triggering the over-temperature warning, the following actions are taken:
|
Default | 005Fh |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
OTW_WARN_EXPONENT | OTW_WARN_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
OTW_WARN_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | OTW_WARN_EXPONENT | R/W | 0000 0 | — | 5-bit, two's complement exponent (scaling factor). |
10:0 | OTW_WARN_MANTISSA | R/W | 000 0101 1111 | — | 11-bit, two's complement mantissa. |
Format | Linear |
Description | The VIN_OV_FAULT_LIMIT command sets the value of the input voltage that causes an input overvoltage fault condition. The default value is 17 V in NVM mode and 14 V in pinstrap mode. Upon triggering an input voltage fault, the following actions are taken:
|
Default | 0011h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
VIN_OVF_EXPONENT | VIN_OVF_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VIN_OVF_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | VIN_OVF_EXPONENT | R/W | 0000 0 | — | 5-bit, two's complement exponent (scaling factor). |
10:0 | VIN_OVF_MANTISSA | R/W | 000 0001 0001 | — | 11-bit, two's complement mantissa. |
After a STORE_DEFAULT_ALL command, the controller reads the last two LSB of VIN_OV_FAULT_LIMIT and convert to decimal, and then adds 14 and converts to save into the VIN_OV_FAULT_LIMIT register. For example, when the two LSB are 01b, after STORE_DEFAULT_ALL command, the VIN_OV_FAULT_LIMIT reads 000Fh (15 V).
Format | Linear |
Description | The IIN_OC_FAULT_LIMIT command sets the value of the input current, in amperes, that the causes an input overcurrent fault condition. Upon triggering the overcurrent fault, the following actions are taken:
|
Default | 00FFh |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
INOCF_LIMIT_EXPONENT | INOCF_LIMIT_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
INOCF_LIMIT_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | INOCF_LIMIT_EXPONENT | R/W | 0000 0 | — | 5-bit, two's complement exponent (scaling factor). |
10:0 | INOCF_LIMIT_MANTISSA | R/W | 000 1111 1111 | — | 11-bit, two's complement mantissa. |
Format | N/A |
Description | The IIN_OC_FAULT_RESPONSE instructs the device on what action to take in response to an input overcurrent fault. Upon triggering the input overcurrent fault, the controller is latched off, and the following actions are taken:
|
Default | C0h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
IIN_OC_FAULT_RESPONSE | |||||||
R-1100 0000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | IIN_OC_FAULT_RESPONSE | R | 1100 0000 | — | Upon triggering the input overcurrent fault, the device will shut down immediately (disables the output), and will not attempt to restart. The output then remains disabled until the fault is cleared. |
Format | Linear |
Description | The IIN_OC_WARN_LIMIT command sets the value of the input current, in amperes, that causes the input overcurrent warning condition. The default setting is 25A. Upon triggering the overcurrent warning, the following actions are taken:
|
Default | 0019h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
INOCW_LIMIT_EXPONENT | INOCW_LIMIT_MANTISSA | ||||||
R/W | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
INOCW_LIMIT_MANTISSA | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | INOCW_LIMIT_EXPONENT | R/W | 0000 0 | — | 5-bit, two's complement exponent (scaling factor). |
10:0 | INOCW_LIMIT_MANTISSA | R/W | 000 0001 1001 | — | 11-bit, two's complement mantissa. |
Format | N/A |
Description | The STATUS_BYTE command returns a single byte of information with the a summary of critical faults. The STATUS_BYTE command is the same register as the low byte of the STATUS_WORD command. It should be noted that all faults and warnings trigger the assertion of PMB_ALERT. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
BUSY | OFF | VOUT_OV | IOUT_OC | VIN_UV | TEMP | CML | OTHER |
R-0 | R | R | R | R | R | R | R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | BUSY | R | 0 | — | Not supported and always set to 0 |
6 | OFF | R | — | This bit is asserted if the unit is not providing power to the output, regardless of the reason, including simply not being enabled. 0: Raw status indicating the IC is providing power to VOUT. 1: Raw status indicating the IC is not providing power to VOUT. |
|
5 | VOUT_OV | R | — | Output Over-Voltage Fault Condition 0: Latched flag indicating no VOUT OV fault has occurred. 1: Latched flag indicating a VOUT OV fault occurred |
|
4 | IOUT_OC | R | — | Output Over-Current Fault Condition 0: Latched flag indicating no IOUT OC fault has occurred. 1: Latched flag indicating an IOUT OC fault has occurred. |
|
3 | VIN_UV | R | — | Input Under-Voltage Fault Condition 0: Latched flag indicating VIN is above the UVLO threshold. 1: Latched flag indicating VIN is below the UVLO threshold. |
|
2 | TEMP | R | — | Over-Temperature Fault/Warning 0: Latched flag indicating no OT fault or warning has occurred. 1: Latched flag indicating an OT fault or warning has occurred. |
|
1 | CML | R | — | Communications, Memory or Logic Fault 0: Latched flag indicating no communication, memory, or logic fault has occurred. 1: Latched flag indicating a communication, memory, or logic fault has occurred. |
|
0 | OTHER | R | — | Other Fault This bit is used to flag faults not covered with the other bit faults. In this case, UVF or OCW faults are examples of other faults not covered by the bits [6:1] in this register. 0: No fault has occurred 1: A fault or warning not listed in bits [6:1] has occurred. |
Format | N/A |
Description | The STATUS_WORD command returns two bytes of information with a summary of critical faults, such as over-voltage, overcurrent, over-temperature, etc. It should be noted that all faults and warnings except VIN_UV trigger the assertion of PMB_ALERT. NOTE: The STATUS_WORD low byte is the STATUS_BYTE. |
Default | 0000h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
VOUT | IOUT | INPUT | MFR | PGOOD | FANS | OTHER | UNKNOWN |
R | R | R | R | R | R-0 | R-0 | R-0 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
BUSY | OFF | VOUT_OV | IOUT_OC | VIN_UV | TEMP | CML | OTHER |
R-0 | R | R | R | R | R | R | R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15 | VOUT | R | — | Output Voltage Fault/Warning 0: Latched flag indicating no VOUT fault or warning has occurred. 1: Latched flag indicating a VOUT fault or warning has occurred. |
|
14 | IOUT | R | — | Output Current Fault/Warning 0: Latched flag indicating no IOUT fault or warning has occurred. 1: Latched flag indicating an IOUT fault or warning has occurred. |
|
13 | INPUT | R | — | Input Voltage/Current Fault/Warning 0: Latched flag indicating no VIN or IIN fault or warning has occurred. 1: Latched flag indicating a VIN or IIN fault or warning has occurred. |
|
12 | MFR | R | — | MFR_SPECIFIC Fault 0: Latched flag indicating no MFR_SPECIFIC fault has occurred. 1: Latched flag indicating a MFR_SPECIFIC fault has occurred. |
|
11 | PGOOD | R | — | Power Good Status 0: Raw status indicating VRRDY pin is at logic high. 1: Raw status indicating VRRDY pin is at logic low. |
|
10 | FANS | R | 0 | — | Not supported and always set to 0. |
9 | OTHER | R | 0 | — | Not supported and always set to 0. |
8 | UNKNOWN | R | 0 | — | Not supported and always set to 0. |
7 | BUSY | R | 0 | — | See information in Table 34 |
6 | OFF | R | — | ||
5 | VOUT_OV | R | — | ||
4 | IOUT_OC | R | — | ||
3 | VIN_UV | R | — | ||
2 | TEMP | R | — | ||
1 | CML | R | — | ||
0 | OTHER | R | — |
Format | N/A |
Description | The STATUS_VOUT command returns one byte of information relating to the status of the converter's output voltage related faults. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_OVF | VOUT_OVW | VOUT_UVW | VOUT_UVF | VOUT_MAXW | TON_MAX | TOFF_MAX | VOUT_TRACK |
R | R-0 | R-0 | R | R | R-0 | R-0 | R-0 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | VOUT_OVF | R | — | Output Over-Voltage Fault 0: Latched flag indicating no VOUT OV fault has occurred. 1: Latched flag indicating a VOUT OV fault has occurred. |
|
6 | VOUT_OVW | R | 0 | — | Not supported and always set to 0. |
5 | VOUT_UVW | R | 0 | — | Not supported and always set to 0. |
4 | VOUT_UVF | R | — | Output Under-Voltage Fault 0: Latched flag indicating no VOUT UV fault has occurred. 1: Latched flag indicating a VOUT UV fault has occurred. |
|
3 | VOUT_MAXW | R | — | VOUT Max Warning 0: Latched flag indicating that no VOUT Max warning has occurred 1: Latched flag indicating that an attempt has been made to set the output voltage to a value higher than allowed by the VOUT_MAX command. |
|
2 | TON_MAX | R | 0 | — | Not supported and always set to 0. |
1 | TOFF_MAX | R | 0 | — | Not supported and always set to 0. |
0 | VOUT_TRACK | R | 0 | — | Not supported and always set to 0. |
Format | N/A |
Description | The STATUS_IOUT command returns one byte of information relating to the status of the converter's output current related faults. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
IOUT_OCF | IOUT_OCUVF | IOUT_OCW | IOUT_UCF | CUR_SHAREF | POW_LIMIT | POUT_OPF | POUT_OPW |
R | R-0 | R | R-0 | R-0 | R-0 | R-0 | R-0 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | IOUT_OCF | R | — | Output Over-Current Fault 0: Latched flag indicating no IOUT OC fault has occurred. 1: Latched flag indicating a IOUT OC fault has occurred . |
|
6 | IOUT_OCUVF | R | 0 | — | Not supported and always set to 0. |
5 | IOUT_OCW | R | — | Output Over-Current Warning 0: Latched flag indicating no IOUT OC warning has occurred 1: Latched flag indicating a IOUT OC warning has occurred |
|
4 | IOUT_UCF | R | 0 | — | Not supported and always set to 0. |
3 | CUR_SHAREF | R | 0 | — | Not supported and always set to 0. |
2 | POW_LIMIT | R | 0 | — | Not supported and always set to 0. |
1 | POUT_OPF | R | 0 | — | Not supported and always set to 0. |
0 | POUT_OPW | R | 0 | — | Not supported and always set to 0. |
Format | N/A |
Description | The STATUS_INPUT command returns one byte of information relating to the status of the converter's input voltage and current related faults. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VIN_OVF | VIN_OVW | VIN_UVW | VIN_UVF | VIN_OFF | IIN_OCF | IIN_OCW | PIN_OPW |
R | R-0 | R-0 | R | R-0 | R | R | R-0 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | VIN_OVF | R | — | Input Over-Voltage Fault 0: Latched flag indicating no VIN OV fault has occurred. 1: Latched flag indicating a VIN OV fault has occurred. |
|
6 | VIN_OVW | R | 0 | — | Not supported and always set to 0. |
5 | VIN_UVW | R | 0 | — | Not supported and always set to 0. |
4 | VIN_UVF | R | — | Input Under-Voltage Fault 0: Latched flag indicating no VIN UV fault has occurred. 1: Latched flag indicating a VIN UV fault has occurred. |
|
3 | VIN_OFF | R | 0 | — | Not supported and always set to 0. |
2 | IIN_OCF | R | — | Input Over-Current Fault 0: Latched flag indicating no IIN OC fault has occurred. 1: Latched flag indicating a IIN OC fault has occurred. |
|
1 | IIN_OCW | R | — | Input Over-Current Warning 0: Latched flag indicating no IIN OC warning has occurred. 1: Latched flag indicating a IIN OC warning has occurred. |
|
0 | PIN_OPW | R | 0 | — | Not supported and always set to 0. |
Format | N/A |
Description | The STATUS_ TEMPERATURE command returns one byte of information relating to the status of the converter's temperature related faults. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
OTF | OTW | UTW | UTF | Reserved | |||
R | R | R-0 | R-0 | R-0000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | OTF | R | — | Over-Temperature Fault 0: Latched flag indicating no temperature fault has occurred. 1: Latched flag indicating a temperature fault has occurred. |
|
6 | OTW | R | — | Over-Temperature Warning 0: Latched flag indicating no temperature warning has occurred. 1: Latched flag indicating a temperature warning has occurred. |
|
5 | UTW | R | 0 | — | Not supported and always set to 0. |
4 | UTF | R | 0 | — | Not supported and always set to 0. |
3-0 | Reserved | R | 0000 | — | Always set to 0. |
Format | N/A |
Description | The STATUS_ CML command returns one byte with contents regarding communication, logic, or memory conditions. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
US_CMD | US_DATA | PEC_FAIL | MEM_FAULT | PRO_FAULT | Reserved | COM_FAIL | CML_OTHER |
R | R | R | R | R-0 | R-0 | R | R-0 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | US_CMD | R | — | Invalid or Unsupported Command Received 0: Latched flag indicating no invalid or unsupported command has received. 1: Latched flag indicating an invalid or unsupported command has received. |
|
6 | US_DATA | R | — | Invalid or Unsupported Data Received 0: Latched flag indicating no invalid or unsupported data has received. 1: Latched flag indicating an invalid or unsupported data has received. |
|
5 | PEC_FAIL | R | — | Packet Error Check Failed 0: Latched flag indicating no packet error check has failed 1: Latched flag indicating a packet error check has failed |
|
4 | MEM_FAULT | R | — | Memory Error 0: Latched flag indicating that there is no memory error. 1: Latched flag indicating that a memory error, i.e. PMBus controller is trying to write into registers when NVM memory is being programmed. |
|
3 | PRO_FAULT | R | 0 | — | Not supported and always set to 0. |
2 | Reserved | R | 0 | — | Always set to 0. |
1 | COM_FAIL | R | — | Other Communication Faults 0: Latched flag indicating no communication fault other than the ones listed in this table has occurred. 1: Latched flag indicating a communication fault other than the ones listed in this table has occurred. |
|
0 | CML_OTHER | R | 0 | — | Not supported and always set to 0. |
Format | N/A |
Description | The STATUS_ MFR_SPECIFIC command returns one byte containing manufacturer-specific faults or warnings. |
Default | 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_FAULT_PS | MFR_PBF | CUR_SH_WARN | RST_VOUT | VOUT_MIN | PHFLT | ||
R | R | R | R | R | R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | MFR_FAULT_PS | R | — | Power State Fault 0: Latched flag indicating no fault from TI power stage has occurred. 1: Latched flag indicating a fault from TI power stage has occurred. |
|
6 | MFR_PBF | R | — | Pre-Bias Fault 0: Latched flag indicating no pre-bias fault (VOUT > 2.75V at startup) has occurred. 1: Latched flag indicating a pre-bias fault (VOUT > 2.75V at startup) has occurred. |
|
5:3 | CUR_SH_WARN | R | 000 | — | not supported and alwats set to 0 |
2 | RST_VOUT | R | — | RST_VOUT Fault 0: Latched flag indicating no RST_VOUT fault has occurred. 1: Latched flag indicating a RST_VOUT fault has occurred. |
|
1 | VOUT_MIN | R | — | VOUT_MIN Fault 0: Latched flag indicating no VOUT_MIN fault has occurred. 1: Latched flag indicating a VOUT_MIN fault has occurred. |
|
0 | PHFLT | R | — | Phase Fault 0: Latched flag indicating no phase fault (no phase pulse detected) has occurred. 1: Latched flag indicating a phase fault (no phase pulse detected) has occurred. |
Format | Linear |
Description | The READ_VIN command returns the input voltage in volts. Refer to Equation 6 to get the real world value. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_VIN_EXPONENT | READ_VIN_MANTISSA | ||||||
R | R | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_VIN_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | READ_VIN_EXPONENT | R | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | READ_VIN_MANTISSA | R | — | 11-bit, two's complement mantissa. |
Format | Linear |
Description | The READ_IIN command returns the input current in amperes. Refer to Equation 6 to get the real world value. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_IIN_EXPONENT | READ_IIN_MANTISSA | ||||||
R | R | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_IIN_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | READ_IIN_EXPONENT | R | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | READ_IIN_MANTISSA | R | — | 11-bit, two's complement mantissa. |
Format | VID |
Description | The READ_VOUT command returns the actual, measured output voltage. |
Default |
Another command, MFR_READ_VOUT (D4h), returns the measured output voltage in linear format.
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_VOUT_VID | |||||||
R | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_VOUT_VID | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:0 | READ_VOUT_VID | R | — | 16-bit, VID format |
Format | Linear |
Description | The READ_IOUT command returns the output current in amperes. Refer to Equation 6 to get the real world value. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_IOUT_EXPONENT | READ_IOUT_MANTISSA | ||||||
R | R | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_IOUT_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | READ_IOUT_EXPONENT | R | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | READ_IOUT_MANTISSA | R | — | 11-bit, two's complement mantissa. |
Format | Linear |
Description | The READ_TEMPERATURE_1 command returns the temperature in degrees Celsius. Refer to Equation 6 to get the real world value. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_TEMP_1_EXPONENT | READ_TEMP_1_MANTISSA | ||||||
R | R | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_TEMP_1_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | READ_TEMP_1_EXPONENT | R | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | READ_TEMP_1_MANTISSA | R | — | 11-bit, two's complement mantissa. |
Format | Linear |
Description | The READ_POUT command returns the output power in watts. Refer to Equation 6 to get the real world value. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_POUT_EXPONENT | READ_POUT_MANTISSA | ||||||
R | R | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_POUT_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | READ_POUT_EXPONENT | R | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | READ_POUT_MANTISSA | R | — | 11-bit, two's complement mantissa. |
Format | Linear |
Description | The READ_PIN command returns the input power in watts. Refer to READ_PIN (97h) to get the real world value. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
READ_PIN_EXPONENT | READ_PIN_MANTISSA | ||||||
R | R | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
READ_PIN_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:11 | READ_PIN_EXPONENT | R | — | 5-bit, two's complement exponent (scaling factor). | |
10:0 | READ_PIN_MANTISSA | R | — | 11-bit, two's complement mantissa. |
Format | N/A |
Description | The PMBus_REVISION command returns the revision of the PMBus to which the device is compliant. |
Default | 11h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
PMBUS_REV | |||||||
R-0001 0001 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | PMBUS_REV | R | 0001 0001 | — | Compliant to revision 1.1 of the PMBus specification. |
Format | N/A |
Description | The MFR_ID command loads the unit with the text character that contains the manufacturer's ID. |
Default | 54h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
MFR_ID_BW | |||||||
R/W | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_ID_HC | |||||||
R-0000 0001 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | MFR_ID_BW | R/W | Yes | PMBus Block Write | |
7:0 | MFR_ID_HC | R | 0000 0001 | — | Hard Coded to 01h |
Format | N/A |
Description | The MFR_MODEL command loads the unit with the text character that contains the model number of the manufacturer. |
Default | NVM: |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
MFR_MODEL_BW | |||||||
R/W | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_MODEL_HC | |||||||
R-0000 0001 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | MFR_MODEL_BW | R/W | Yes | PMBus Block Write | |
7:0 | MFR_MODEL_HC | R | 0000 0001 | — | Hard Coded to 01h |
Format | N/A |
Description | The MFR_REVISION command loads the unit with the text character that contains the revision number of the manufacturer. This is typically done once at the time of manufacture. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
MFR_REVISION_HC1 | MFR_REVISION_BW | ||||||
R-0000 | R/W | ||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_REVISION_HC2 | |||||||
R-0000 0001 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:12 | MFR_REVISION _HC1 | R | 0001 | — | Hard Coded to 0h |
11:8 | MFR_REVISION | R/W | Yes | PMBus Block Write | |
7:0 | MFR_REVISION_HC2 | R | 0000 0001 | — | Hard Coded to 01h |
Format | N/A |
Description | The MFR_DATE command loads the unit with the text character that identifies the device's date of manufacture. This is typically done once at the time of manufacture. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
MFR_DATE_BW | |||||||
R/W | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_DATE_HC | |||||||
R-0000 0001 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | MFR_DATE_BW | R/W | Yes | PMBus Block Write | |
7:0 | MFR_DATE_HC | R | 0000 0001 | — | Hard Coded to 01h. |
Format | VID |
Description | The MFR_VOUT_MIN command sets an lower limit on the output voltage that the unit can command regardless of any other commands or combinations. The intent of this command is to provide a safeguard against a user accidentally setting the output voltage to a possibly non-operational level. The device detects that an attempt has been made to program the output to a voltage lower than the value set by the MFR_VOUT_MIN command. The device treats this detection as a warning condition and not a fault condition. If an attempt is made to program the output voltage lower than the limit set by this command, the device responds as follows:
|
Default | 0000h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
RESERVED | |||||||
R-0000 0000 | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_VOUT_MIN | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | RESERVED | R | 0000 0000 | — | Hard coded to 00h |
7:0 | MFR_VOUT_MIN | R/W | 0000 0000 | — | Minimum value for VID |
Format | N/A |
Description | The MFR_SPECIFIC_00 command sets the valley-current threshold for the per-phase overcurrent limit. The settings can override the default setting form the OCL-R pin. |
Default | Pin strap: OCL-R pin NVM: 08h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | OCL | ||||||
R-0000 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:4 | Reserved | R | R-0000 | — | Always set to 0. |
3:0 | OCL | R/W | Yes | 0000: 24A 0001: 27A 0010: 30A 0011: 33A 0100: 36A 0101: 39A 0110: 42A 0111: 45A 1000: 48A 1001: 51A 1010: 54A 1011: 57A 1100: 60A 1101: 63A 1110: 66A 1111:69A |
Format | |
Description | The MFR_SPECIFIC_01 command sets the averaging time for telemetry reporting. |
Default | 50h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | FILTER_PIN | Reserved | FILTER_IV | ||||
R-0 | R/W | R-00 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | Reserved | R | 0 | — | Always set to 0. |
6:4 | FILTER_PIN | R/W | 101 | — | Averaging Time for Input Power Reporting 000: Bypass. 001: 2 ms 010: 5.5 m 011: 11.5 m 100: 19 ms 101: 50 ms 110: 100 ms 111: 225 ms |
3:2 | Reserved | R | 00 | — | Always set to 0. |
1:0 | FILTER_IV | R/W | 00 | — | Averaging Time for Current and Voltage Reporting 00: Bypass. 01: .5 ms 10: 1 ms 11: 2.5 ms |
Format | Linear |
Description | The MFR_SPECIFIC_04 command returns the actual, measured output voltage in volts. Refer to Equation 6 to get the real world value, where n= -9. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
MFR_SPEC_04_MANTISSA | |||||||
R | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
MFR_SPEC_04_MANTISSA | |||||||
R |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:0 | MFR_SPEC_04_MANTISSA | R | — | Unsigned 16-bit mantissa with an exponent value of n=-9. |
Format | Signed Two's Complement |
Description | The MFR_SPECIFIC_05 command is used to trim the VR output voltage in volts. LSB resolution is 5 mV/10 mV based on the selected VR12.0/VR12.5. |
Default | NVM: 00h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VOUT_VID_OFFSET | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | VOUT_VID_OFFSET | R/W | Yes | Sets the VR output trim voltage. 01111111: 0.635 V in VR12.0 and 1.27V in VR12.5 01111110: 0.630 V in VR12.0 and 1.26 V in VR12.5 ........................... 00000001: 0.005 V in VR12.0 and 0.01 V in VR12.5 00000000: 0 V 11111111: –0.005 V in VR12.0 and –0.01 V in VR12.5 ........................... 10000001: –0.635 V in VR12.0 and –1.27 V in VR12.5 10000000: –0.640 V in VR12.0 and –1.28 V in VR12.5 |
Format | N/A |
Description | The MFR_SPECIFIC_07 command sets the additional function bits. |
Default | NVM: 02h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | OVFLT_MODE_SEL | PS_FLT_DIS | SLEW_FAST | OSR_TRISTATE | SST_TIME | ||
R-0000 0 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:5 | Reserved | R | 000 | — | Always set to 0. |
4 | OVFLT_MODE_SEL | R/W | No | 0: Tracking OVP and Fixed OVP is 3 cycle hiccup then latch off 1: Tracking OVP and Fixed OVP is latch off from first occurrence. | |
3 | PS_FLT_DIS | R/W | No | 0: Power stage fault is active 1: Power stage fault is disabled | |
2 | SLEW_FAST | R/W | Yes | Fast Slew Mode Enable/Disable 0: Default slew rate selected by MFR_SPECIFIC_13[2:0] 1: Add 1.36 mV/µs to the selected slew rate |
|
1 | OSR_TRISTATE | R/W | Yes | Body Braking Enable/Disable 0: Enable OSR pulse truncation without body braking 1: Enable OSR pulse truncation with body braking |
|
0 | SST_TIME | R/W | Yes | Soft Slew Rate Selection 0: soft start slew rate dependent on TRISE 1: 1/16 of the selected slew rate for soft-start |
Format | N/A |
Description | The MFR_SPECIFIC_08 command sets the load line as percentage of the default one. For example, if slope is set as 1mohm = 100%, then 0.5mohm = 50% |
Default | 04h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
DROOP | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | DROOP | R/W | 0000 0100 | — | 0000 0000: 0% 0000 0001: 25% 0000 0010: 50% 0000 0011: 75% 0000 0100: 100% 0001 0000: 80% 0010 0000: 85% 0011 0000: 90% 0100 0000: 95% 0101 0000: 105% 0110 0000: 110% 0111 0000: 115% 1000 0000: 120% 1001 0000: 125% 1010 0000: 150% 1011 0000: 175% Others: 100% |
Format | N/A |
Description | The MFR_SPECIFIC_09 command sets the threshold for OSR and USR control. The setting can override the default setting from the O-USR pin. |
Default | Pin strap: O-USR pin NVM: 77h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | USR | Reserved | OSR | ||||
R-0 | R/W | R-0 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | Reserved | R | 0 | — | Always set to 0. |
6:4 | USR | R/W | Yes | Undershoot Reduction 000: 20 mV 001: 30 mV 010: 60 mV 011: 80 mV 100: 100 mV 101: 120 mV 110: 140 mV 111: USR off |
|
3 | Reserved | R | 0 | — | Always set to 0. |
2:0 | OSR | R/W | Yes | Overshoot Reduction 000: 30 mV 001: 40 mV 010: 60 mV 011: 80 mV 100: 100 mV 101: 120 mV 110: 140 mV 111: OSR off |
Format | N/A |
Description | The MFR_SPECIFIC_10 command sets the maximum operating current (IMAX, unit: A) of the converter. The setting can override the default setting from the F-IMAX pin |
Default | Pin strap: F-IMAX pin NVM: |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
IMAX | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | IMAX | R/W | Yes | Set maximum operating current. |
Format | VID |
Description | The MFR_SPECIFIC_11 command sets the boot voltage in 8-bit VID format. The setting can override the default setting from the VBOOT pin. |
Default | Pin strap: VBOOT pin NVM: 97h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VBOOT | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:0 | VBOOT | R/W | Yes | Set the boot voltage according to the selected VID table. |
Format | N/A |
Description | The MFR_SPECIFIC_12 command sets the switching frequency and the soft start rise slew rate. The settings can override the default setting from the F-IMAX. |
Default | Pin strap: F-IMAX pin NVM: 20h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
FSW | Reserved | TRISE | |||||
R/W | R-0 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:4 | FSW | R/W | Yes | Switching Frequency 0000: 300 kHz 0001: 400 kHz 0010: 500 kHz 0011: 600 kHz 0100: 700 kHz 0101: 800 kHz 0110: 900 kHz 0111: 1000 kHz 1000: 350 kHz 1001: 450 kHz 1010: 550 kHz 1011: 650 kHz 1100: 750 kHz 1101: 850 kHz 1110: 950 kHz 1111: 1000 kHz |
|
3:2 | Reserved | R | 0 | — | Always set to 0. |
1:0 | TRISE | R/W | Yes | Soft start rise slew rate in terms of VOUT slew rate 00: 1 01: 1/2 10: 1/4 11: 1/8 |
Format | N/A |
Description | The MFR_SPECIFIC_13 command sets the slew rates and the operation modes. The settings can override the default setting from the SLEW-MODE pin. |
Default | Pin strap: SLEW-MODE pin NVM: 89h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
VR12_MODE | PI_SET | Reserved | DPS_EN | ZLL_SET | SLEW | ||
R/W | R/W | R/W | R/W | R/W | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7 | VR12_MODE | R/W | Yes | VR12 Mode 0: VR12.5. 1: VR12.0. |
|
6 | PI_SET | R/W | Yes | Phase Interleaving 0: 1: 1/3, 2/4 and 5/6 phase interleaving |
|
5 | Reserved | R/W | Yes | Not used, write or read has no effect | |
4 | DPS_EN | R/W | Yes | Dynamic Phase Shedding Enable 0: Disable dynamic phase shedding. 1: Enable dynamic phase shedding. |
|
3 | ZLL_SET | R/W | Yes | Load Line 0: Non-zero load line 1: Zero load line |
|
2:0 | SLEW | R/W | Yes | Slew Rate 000: 0.34 mV/µs 001: 0.68 mV/µs 010: 1.02 mV/µs 011: 1.36 mV/µs 100: 1.7 mV/µs 101: 2.04 mV/µs 110: 2.38 mV/µs 111: 2.74 mV/µs |
Format | N/A |
Description | The MFR_SPECIFIC_14 command sets the ramp amplitude for compensations. The settings can override the default setting from the OCL-R pin. |
Default | Pin strap: OCL-R pin NVM: 06h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | RAMP | ||||||
R-0000 0 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:3 | Reserved | R | 0 | — | Always set to 0. |
2:0 | RAMP | R/W | Yes | Ramp Amplitude 000: 20 mVPP 001: 40 mVPP 010: 60 mVPP 011: 80 mVPP 100: 100 mVPP 101: 120 mVPP 110: 150 mVPP 111: 200 mVPP |
Format | N/A |
Description | The MFR_SPECIFIC_15 command sets the threshold for the dynamic phase shedding. Use 4 × overcurrent limit (OCL) as 100% load condition |
Default | NVM: 01h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | DPS_TH_LOW | DPS_TH_HIGH | |||||
R-0000 | R/W | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:4 | Reserved | R | 0000 | — | Always set to 0. |
3 | DPS_TH_LOW | R/W | Yes | Switch from 2 Phase to 1 Phase Operation 0: Disable decreasing to 1 phase operation. 1: 10% load. |
|
2:0 | DPS_TH_HIGH | R/W | Yes | Switch from 6 Phase to 2 Phase Operation 000: 15% load. 001: 20% load. 010: 25% load. 011: 30% load. Others: 35% load. |
Format | N/A |
Description | The MFR_SPECIFIC_16 command sets the threshold for the VIN Undervoltage Lockout (UVLO). |
Default | NVM: 01h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | VIN_UVLO | ||||||
R-00 0000 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:2 | Reserved | R | 00 0000 | — | Always set to 0. |
1:0 | VIN_UVLO | R/W | 01 | Yes | Input Voltage UVLO 00:4.25V 01: 6.0V 10: 8.1V 11: 10.2V |
Format | N/A |
Description | The MFR_SPECIFIC_19 command sets the thresholds for determining the current sharing warning. Once the difference between any phase current and the average current is larger than the pre-defined threshold, the STATUS_IOUT [3] will be set while asserting PMB_ALERT#. |
Default | 0003h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
Reserved | |||||||
R- 0000 0000 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
PHFLT_DIS_SEL | Reserved | CUR_SHARE_TH | |||||
R/W | R- 0000 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | Reserved | R | 0000 0000 | __ | Always set to 0. |
7 | PHFLT_DIS_SEL | R/W | 0 | Yes | 0: Phase with Current Share Warning will be turned off. 1: Phase with Current Share Warning will NOT be turned off. |
6:3 | Reserved | R | 0000 | — | Always set to 0. |
2:0 | CUR_SHARE_TH | R/W | 011 | Yes | 000: 2 Amps 001: 4 Amps 010: 6 Amps011: 8 Amps 000: 10 Amps001: 15 Amps 010: 20 Amps011: OFF |
Format | N/A |
Description | The MFR_SPECIFIC_20 command sets the maximum operational phase numbers on-the-fly. If the maximum operational phase number is set higher than the available phase numbers specified by hardware, then the operational phase number remains unchanged, and the STAUTS_MFR_SPECIFIC<3> is set while asserting PMB_ALERT. |
Default | Hardware Specific |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | PHASE_NUM | ||||||
R-0 0000 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:3 | Reserved | R | 0 0000 | — | Always set to 0. |
2:0 | PHASE_NUM | R/W | — | Phase Number 000: 1-phase operation. 001: 2-phase operation. 010: 3-phase operation. 011: 4-phase operation. 100: 5-phase operation. 101: 6-phase operation. Others: Not allowed |
Format | N/A |
Description | The MFR_SPECIFIC_21 command programs the over-voltage thresholds. Tracking OV threshold: VOUT_COMMAND + OV_TRACK_OFFSET Fixed OV threshold: VOUT_MAX + FIX_OV_OFFSET |
Default | 0Fh |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | OV_TRACK_OFFSET | FI_OV_OFFSET | |||||
R-000 | R/W | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:5 | Reserved | R | 000 | — | Always set to 0. |
4:3 | OV_TRACK_OFFSET | Yes | 00:175mV 01:225mV 10:275mV11:325 mV |
||
2:0 | FIX_OV_OFFSET | Yes | 000: 50mV 001: 100mV 010: 150mV011: 200mV 100: 250mV101: 300mV 110: 350mV111: 400mV |
Format | N/A |
Description | The MFR_SPECIFIC_22 command sets the value of VOUT undervoltage threshold. UVP threshold = VOUT_COMMAND - Load Line * Iout - VOUT_UVF_OFFSET |
Default | NVM: 03h |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | VOUT_UVF_THRESHOLD | ||||||
R-0 0000 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:3 | Reserved | R | 0 0000 | — | Always set to 0. |
2:0 | VOUT_UVF_OFFSET | R/W | Yes | VOUT UVF threshold 000: 50 mV 001: 100 mV 010: 150 mV 011: 200 mV 100: 250 mV 101: 300 mV 110: 325 mV 111: 400 mV |
Format | N/A |
Description | The MFR_SPECIFIC_23 command sets the boot voltage in 8-bit VID format. (Same as MFR_SPECIFIC_11) The two data bytes contain of a right-justified VID code with VID0 in bit 0 of the lower data byte, VID1 in bit 1 of the lower byte and so forth. |
Default |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
Reserved | |||||||
R- 0000 0000 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
BOOT_CODE | |||||||
R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:8 | Reserved | R | 0000 0000 | __ | Always set to 0. |
7:0 | BOOT_CODE | R/W | Yes | Set the boot voltage according to the selected VID table. |
Format | N/A |
Description | The MFR_SPECIFIC_24 command set is used to enable/disable the Phases in Analog along with some other settings/logic. |
Default |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Reserved | PH5_DIS | PH4_DIS | PH3_DIS | PH2_DIS | PH1_DIS | PH0_DIS | |
R-00 | R/W |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
7:6 | Reserved | R | 00 | — | Always set to 0. |
5 | PH5_DIS | R/W | 0 | No | 1: Phase5 is disabled. 0: Phase5 is not disabled. |
4 | PH4_DIS | R/W | 0 | No | 1: Phase4 is disabled. 0: Phase4 is not disabled. |
3 | PH3_DIS | R/W | 0 | No | 1: Phase3 is disabled. 0: Phase3 is not disabled. |
2 | PH2_DIS | R/W | 0 | No | 1: Phase2 is disabled. 0: Phase2 is not disabled. |
1 | PH1_DIS | R/W | 0 | No | 1: Phase1 is disabled. 0: Phase1 is not disabled. |
0 | PH0_DIS | R/W | 0 | No | 1: Phase0 is disabled. 0: Phase0 is not disabled. |
Format | |
Description | The MFR_SPECIFIC_44 command reads back the DEVICE_CODE information. |
Default | 01F8h |
15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
DEVICE_CODE | |||||||
R-0000 0001 | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
DEVICE_CODE | |||||||
R-1111 0000 |
Bit | Field | Type | Reset | NVM | Description |
---|---|---|---|---|---|
15:0 | DEVICE_CODE | R | 0000 0001 1111 0000 | — | Device Code |