SLUA888 May 2018 TPS53622 , TPS53659 , TPS53679 , TPS53681
Table 4 gives an example configuration that contains all programmable parameters in a VR13 controller device. Every application has different data. All other parameters stored in configuration files are either calculated, measured, or derived from these values. The Fusion Digital Power Designer GUI displays block commands in ascending order of significance (for example byte 0, byte 1, ...). The GUI displays word commands in descending significance (for example byte 1, byte 0).
PMBus Command | Transaction Type | CMD Code (hex) | Example Value (hex) |
---|---|---|---|
USER_DATA_00 | Block Write, Block Read | B0h | 1410020030F5 |
USER_DATA_01 | Block Write, Block Read | B1h | 000000000040 |
USER_DATA_02 | Block Write, Block Read | B2h | 8904000000D0 |
USER_DATA_03 | Block Write, Block Read | B3h | 030010050080 |
USER_DATA_04 | Block Write, Block Read | B4h | 0906C325C777 |
USER_DATA_05 | Block Write, Block Read | B5h | E408C57983E1 |
USER_DATA_06 | Block Write, Block Read | B6h | 85DA1112E87F |
USER_DATA_07 | Block Write, Block Read | B7h | 804B051053FA |
USER_DATA_08 | Block Write, Block Read | B8h | 0000000000A6 |
USER_DATA_09 | Block Write, Block Read | B9h | 000170848080 |
USER_DATA_10 | Block Write, Block Read | BAh | 00262EC0C185 |
USER_DATA_11 | Block Write, Block Read | BBh | 080220C08FE1 |
USER_DATA_12 | Block Write, Block Read | BCh | 40F08D20FF01 |
VOUT_MAX[PAGE 0] | Write Word, Read Word | 24h | 00FF |
VOUT_MAX[PAGE 1] | Write Word, Read Word | 24h | 00FF |
MFR_SERIAL | Block Write, Block Read | 9Eh | 05C60AD2 |