TIDUF99 November 2024
Testing the PLC hardware implementation includes validating the coupling circuit and the band-pass filter in the receive path.
To check the coupling circuit, the impedance was measured using a frequency response analyzer (Venable Instruments Model 3120). Importantly, the coupling network needs to present a high impedance at the PLC carrier frequencies and maintains lower impedances outside the communication band. Figure 4-12 shows the measured impedance. Yellow markers highlight the impedance at the mark and space frequencies of the RSD PLC protocol.
An additional band-pass filter is implemented in the receive path. In this path it is important that the pass band is set to the carrier frequencies of the PLC communication. Figure 4-13 shows the measured transfer curve of the bandpass filter. The pass band is located between 70kHz and 150kHz. The same frequency response analyzer was used for this measurement.
This design verified the PLC coupling circuit and AFE031 with rapid shutdown function in combination with the TIDA-060001 reference design. See also SunSpec Rapid Shutdown Transmit and Receive Reference Design.