概要
The TIDA-01088 reference design implements power quality parameter measurement in a polyphase energy measurement system. Total harmonic distortion (THD), fundamental readings, and standard metrology parameters such as active and reactive energy and power are calculated. Phase to phase angles are also calculated to help prevent incorrect installation of the system. This design uses isolated shunt current sensors to maintain accuracy in harmonic analysis and also immunity from magnetic tamper attacks.
特長
- Class 0.5% Three-phase metrology with galvanically isolated shunt current sensors
- Isolation performance of up to 1-kV AC (working voltage) and 7 kV (Peak)
- Total Harmonic Distortion (THD) calculated for Voltage and Current
- Voltage Sag and Swell events logged with programmable threshold levels
- Phase to Phase angle measurement for determining phase sequence to help prevent incorrect installation of system
- Complete Energy Library with Fundamental Voltage and Current, Fundamental Active and Reactive power, Active and Reactive Energy, Root Mean Square(RMS) Current and Voltage, Power Factor, and Line Frequency
組み立てられたボードは、テストと性能検証のみの目的で開発されたものであり、販売していません。
設計ファイルと製品
設計ファイル
すぐに使用できるシステム・ファイルをダウンロードすると、設計プロセスを迅速化できます。
TIDRLM8.PDF (250 K)
設計に使用したコンポーネント、参照指定子、メーカー名や型番などを記入した詳細なリスト
製品
設計や代替製品候補に TI 製品を含めます。
MSP430 マイコン
MSP430F67641 — 3 個のデルタ・シグマ ADC、10 ビット SAR ADC、LCD、128KB フラッシュ、8KB RAM 搭載、低コスト、多相メータリング SoC
データシート: PDF | HTML開発を始める
サポート・ソフトウェア
技術資料
= TI が選択した主要ドキュメント
結果が見つかりませんでした。検索条件をクリアして、もう一度検索を行ってください。
すべて表示 2
種類 | タイトル | 英語版のダウンロード | 日付 | |||
---|---|---|---|---|---|---|
* | 設計ガイド | Multi-Phase Power Quality Measurement With Isolated Shunt Sensors Design Guide (Rev. A) | 2016年 7月 26日 | |||
技術記事 | Quantifying harmonic distortion - Effect of sinc3 filter roll off (part 3) | PDF | HTML | 2017年 8月 7日 |